A Comprehensive Study on the Effects of Surface Roughness on Power Consumption and Heat Transfer Performance in Novel In-Tube Condensation r123yf Refrigerant Systems

Jump To References Section

Authors

  • Department of Mechanical Engineering, Vidyavardhaka College of Engineering, Mysore - 570030, Karnataka ,IN
  • Department of Mechanical Engineering, Vidyavardhaka College of Engineering, Mysore - 570030, Karnataka ,IN
  • Department of Mechanical Engineering, Vidyavardhaka College of Engineering, Mysore - 570030, Karnataka ,IN

DOI:

https://doi.org/10.18311/jmmf/2023/36264

Keywords:

Condensation Heat Transfer, Optimal Surface Roughness, Power Consumption, R123yf Refrigerant, Surface Roughness

Abstract

This study investigates the impact of surface roughness on the condensation Heat Transfer Coefficient (HTC) of R123yf refrigerant in a uniquely designed test rig with pre-condenser and post-condenser for quality regulation. In mining industries, the mining equipment consumes more amount to power for the Air Conditioning system. To reduce the power consumption of copper metal inside the surface morphology needs to be changed. Experiments were conducted in a 750 mm long, 8.4 mm internal diameter copper tube, with regard to mass flux varying from 150 kg.m-2.s-1 to 300 kg.m-2.s-1, refrigerant quality varying from 0.3 to 0.8, and saturated temperature from 35°C to 45°C. The impact of varying surface roughness (1.5 μm, 2.5μm, 3.4 μm, and 6.7 μm) on HTC was examined. The plane tube condensation experimental results agreed with M M Shah's heat transfer coefficient correlations, with a 20% absolute mean deviation. It was observed that increasing surface roughness enhanced the HTC. The optimal surface roughness was determined to be 3.4 μm, as it resulted in a significant increase in HTC (26.25%) with a moderate rise in power consumption (15.40%). Higher surface roughness led to a drastic increase in power consumption, making it less desirable for practical applications. Through a systematic analysis of the experimental data, this study identifies the critical trade-off between surface roughness and power consumption, providing guidance for the design of energy-efficient condensation heat transfer systems using R123yf refrigerant. By pinpointing an optimal surface roughness for copper tubes used in refrigeration, this study offers a pragmatic solution for enhancing the efficiency of air conditioning systems in mining equipment, a sector notorious for high energy expenditures. The findings indicate a direct application in mining operations where equipment cooling demands contribute significantly to energy consumption. Implementing the recommended surface modifications can lead to substantial energy savings, thereby reducing operational costs and improving the sustainability of mining activities. Furthermore, the adaptation of R123yf refrigerant systems with optimized surface roughness could serve as a model for energy conservation measures across various facets of the mining industry..

Downloads

Download data is not yet available.

Metrics

Metrics Loading ...

Downloads

Published

2023-11-30

How to Cite

Muthuraju, N. P., Sadashive Gowda , B., & Gurudatt, H. M. (2023). A Comprehensive Study on the Effects of Surface Roughness on Power Consumption and Heat Transfer Performance in Novel In-Tube Condensation r123yf Refrigerant Systems. Journal of Mines, Metals and Fuels, 71(11), 1954–1961. https://doi.org/10.18311/jmmf/2023/36264

 

References

Evans O. The abortion of the young steam engineer’s guide: containing an investigation of the principles, con- struction and powers of steam engines.... Illustrated with Five Engravings. Author; 1805.

Perkins J. Apparatus for producing ice and cooling flu- ids. Patent 6662. United Kingdom; 1834.

Lighting C. Power Company (CLPC). Advertisement, Ice and Refrigeration. 1922; 28.

Midgley Jr T, Henne AL. Organic fluorides as refriger- ants. Ind Eng Chem. 1930; 22(5):542-545. DOI: https://doi.org/10.1021/ie50245a031

Downing R. History of the organic fluorine industry. Kirk-Othmer Encyclopedia of Chemical Technology. 1966; 9:704-707.

Shah MM. A general correlation for heat transfer during film condensation inside pipes. Int J Heat Mass Transfer. 1979; 22(4):547-556. DOI: https://doi.org/10.1016/0017-9310(79)90058-9

Haaland SE. Simple and explicit formulas for the friction factor in turbulent pipe flow. 1983. DOI: https://doi.org/10.1115/1.3240948

Downing R. Development of chlorofluorocarbon refrig- erants. ASHRAE transactions. 1984; 90(2):481-491.

Moffat RJ. Describing the uncertainties in experimental results. Exp Thermal Fluid Sci. 1988; 1(1):3-17. DOI: https://doi.org/10.1016/0894-1777(88)90043-X

UNFCCC U. Kyoto protocol to the United Nations framework convention on climate change. Proceedings of the 3rd Conference of the Parties, FCCC/CP/1997/L. 7/Add. 1, United Nations Framework Convention on Climate Change. 1997.

Secretariat O. The Montreal protocol on substances that deplete the ozone layer. United Nations Environment Programme, Nairobi, Kenya; 2000.

Secretariat UNEP O. Montreal protocol on substances that deplete the ozone layer as either adjusted and/or amended in London 1990, Copenhagen 1992, Vienna 1995, Montreal 1997, Beijing 1999, Incumbent; 2000.

Minor B, Spatz M. HFO-1234yf low GWP refrigerant update. 2008.

Schuster P, et al. Biotransformation of 2, 3, 3, 3-tetra- fluoropropene (HFO-1234yf). Toxicol Appl Pharmacol. 2008; 233(2):323-332. DOI: https://doi.org/10.1016/j.taap.2008.08.018

Koban M. HFO-1234yf low GWP refrigerant LCCP analysis. SAE International; 2009. DOI: https://doi.org/10.4271/2009-01-0179

Takizawa K, et al. Flammability assessment of CH2CFCF3: Comparison with fluoroalkenes and fluoroalkanes. J Hazard Mater. 2009; 172(2-3):1329-1338. DOI: https://doi.org/10.1016/j.jhazmat.2009.08.001

Akasaka R, et al. Thermodynamic property modeling for 2, 3, 3, 3-tetrafluoropropene (HFO-1234yf). Int J Refrigeration. 2010; 33(1):52-60. DOI: https://doi.org/10.1016/j.ijrefrig.2009.09.004

Brown JS, et al. Thermodynamic properties of eight fluorinated olefins. Int J Refrigeration. 2010; 33(2):235-241. DOI: https://doi.org/10.1016/j.ijrefrig.2009.04.005

Del Col D, et al. Heat transfer and pressure drop during condensation of the low GWP refrigerant R1234yf. Int J Refrigeration. 2010; 33(7):1307-1318. DOI: https://doi.org/10.1016/j.ijrefrig.2010.07.020

Di Nicola C, et al. P−V−T behavior of 2, 3, 3, 3-Tetrafluoroprop-1-ene (HFO-1234yf) in the vapor phase from (243 to 373) K. J Chem Eng Data. 2010; 55(9):3302-3306. DOI: https://doi.org/10.1021/je100102q

Fujitaka A, et al. Application of low global warming potential refrigerants for room air conditioners. 2010 International Symposium on Next-generation Air Conditioning and Refrigeration Technology, Tokyo, Japan; 2010.

Minor BH, et al. Flammability characteristics of HFO‐1234yf. Process Safety Progress. 2010; 29(2):150- 154. DOI: https://doi.org/10.1002/prs.10347

Park K-J, Jung D. Nucleate boiling heat transfer coef- ficients of R1234yf on plain and low fin surfaces. Int J Refrigeration. 2010; 33(3):553-557. DOI: https://doi.org/10.1016/j.ijrefrig.2009.12.020

Tanaka K, Higashi Y. Thermodynamic properties of HFO-1234yf (2, 3, 3, 3-tetrafluoropropene). Int J Refrigeration. 2010; 33(3):474-479. DOI: https://doi.org/10.1016/j.ijrefrig.2009.10.003

Ziegler F. The multiple meanings of the Stefan-number (and relatives) in refrigeration. Int J Refrigeration. 2010; 33(7):1343-1349. DOI: https://doi.org/10.1016/j.ijrefrig.2010.06.015

Zilio C, et al. Experimental analysis of a minichannel air cooled condenser operating with R1234yf. The 23rd IIR International Congress of Refrigeration. Prague, Czech Republic; 2011.

Kazakov A, et al. Computational design of new refrig- erant fluids based on environmental, safety, and thermodynamic characteristics. Ind Eng Chem Res. 2012; 51(38):12537-12548. DOI: https://doi.org/10.1021/ie3016126

Hodnebrog Ø, et al. Global warming potentials and radi- ative efficiencies of halocarbons and related compounds: A comprehensive review. Rev Geophys. 2013; 51(2):300-378. DOI: https://doi.org/10.1002/rog.20013

Bobbo S, et al. R1234yf as a substitute of R134a in auto- motive air conditioning. Solubility measurements in two commercial PAG oils. Int J Refrigeration. 2014; 40:302-308. DOI: https://doi.org/10.1016/j.ijrefrig.2013.08.002

McLinden MO, et al. A thermodynamic analysis of refrigerants: possibilities and tradeoffs for low-GWP refrigerants. Int J Refrigeration. 2014; 38:80-92. DOI: https://doi.org/10.1016/j.ijrefrig.2013.09.032

Janković Z, et al. Thermodynamic and heat trans- fer analyses for R1234yf and R1234ze (E) as drop-in replacements for R134a in a small power refrigerating system. Appl Thermal Eng. 2015; 80:42-54. DOI: https://doi.org/10.1016/j.applthermaleng.2015.01.041

Qi Z. Performance improvement potentials of R1234yf mobile air conditioning system. Int J Refrigeration. 2015; 58:35-40. DOI: https://doi.org/10.1016/j.ijrefrig.2015.03.019

Huber ML, Assael MJ. Correlations for the viscosity of 2, 3, 3, 3-tetrafluoroprop-1-ene (R1234yf ) and trans-1, 3, 3, 3

tetrafluoropropene (R1234ze (E)). Int J Refrigeration. 2016; 71:39-45. DOI: https://doi.org/10.1016/j.ijrefrig.2016.08.007

Klein S, Alvarado F. Engineering equation solver, ver- sion 10.047. F-Chart Software; 2016.

Mendoza-Miranda JM, et al. Comparative evaluation of R1234yf, R1234ze (E) and R450A as alternatives to R134a in a variable speed reciprocating compressor. Energy. 2016; 114:753-766. DOI: https://doi.org/10.1016/j.energy.2016.08.050

Shah MM. Comprehensive correlations for heat transfer during condensation in conventional and mini/micro channels in all orientations. Int J Refrigeration. 2016; 67:22-41. DOI.org/10.1016/j.ijrefrig.2016.03.014. DOI: https://doi.org/10.1016/j.ijrefrig.2016.03.014