Study on Voltage Stability of Transmission Lines Under Large Reactive Power Burden

Jump To References Section

Authors

  • HETC, Hooghly ,IN
  • Jadavpur University ,IN
  • AOT, Aedconagar (formerly at Jadavpur University) ,IN

DOI:

https://doi.org/10.24906/isc/2013/v27/i3/177595

Abstract

In this paper, the results of load flow studies on a fictitious 6-bus system under conditions of large reactive power burden and reactive power mismatch have been presented. With increasing reactive power burden and reactive power mismatch, it has been noted that the voltage profile becomes poorer and poorer eventually leading to voltage collapse. Even before a collapse, the voltage profile becomes unacceptably poor. All bus voltages fall below 0.95 p.u. It has been indicated that the load flow must be planned with a look to this phenomenon. The role of series and shunt compensators has also been highlighted in this context.

Downloads

Download data is not yet available.

Downloads

Published

2013-05-01

How to Cite

Maity, A., Bhattacharya, K., & Sanyal, A. N. (2013). Study on Voltage Stability of Transmission Lines Under Large Reactive Power Burden. Indian Science Cruiser, 27(3), 26–32. https://doi.org/10.24906/isc/2013/v27/i3/177595